Fresh air for tight New York homes with ERVs, HRVs, range-hood makeup air, bath exhaust and filtration
Updated October 25, 2026
Summary
Once a home is air-sealed, re-windowed or gut-renovated, it needs planned mechanical ventilation. For most New York City and Long Island homes, a balanced energy recovery ventilator (ERV) is the default choice because it retains some winter moisture and reduces summer humidity from incoming air. Powerful range hoods need makeup air, and New York City's Mechanical Code sets its own requirement, separate from the rest of the state, which we confirm during design. Good bath exhaust and MERV 13 filtration complete the system.
Why a tighter home needs planned ventilation
Air sealing, new windows, spray foam and dense-pack insulation reduce the accidental air exchange that once ventilated older houses. That saves energy, but moisture, carbon dioxide, odors, cooking particles and, in homes with gas ranges, nitrogen dioxide now stay indoors longer.
Current energy codes pair tighter construction with whole-house mechanical ventilation. In practice, any gut renovation of a brownstone, a Queens two-family house or a Long Island cape that includes new windows and insulation should include a ventilation plan from the start, before walls and ceilings are closed.
How much fresh air a home needs
The national reference for residential ventilation is ASHRAE Standard 62.2, which the NYC Mechanical Code references for dwelling units. Its whole-house formula is 0.03 cfm per square foot of floor area plus 7.5 cfm per person, with occupancy taken as the number of bedrooms plus one. A 2,000 square foot house with three bedrooms therefore needs about 60 plus 30, or 90 cfm of continuous ventilation.
The standard allows a credit for measured air leakage in single-family homes, based on a blower-door test, but not for apartments in multifamily buildings. Model codes also allow intermittent operation if the fan is sized up to deliver the same daily volume. The applicable code edition differs between New York City and the rest of the state, and we design to the edition that governs your property.
Three ventilation strategies and how each behaves in New York
| Strategy | How it works | Effect in a New York winter | Best suited to |
|---|---|---|---|
| Exhaust-only | A quiet bath fan runs continuously and air enters through gaps | Depressurizes the house, pulling cold air through walls, the garage or the basement, and can backdraft natural-draft water heaters and boilers | Small, all-electric homes and apartments with no atmospheric appliances |
| Supply-only | An outdoor-air duct with a motorized damper feeds the furnace return | Slightly pressurizes the house, pushing warm moist air into walls and attics, and can over-dry the house if the damper is not controlled | Forced-air houses on a limited budget, with careful controls |
| Balanced (ERV or HRV) | Separate fans supply and exhaust equal amounts of air through a heat exchange core | Neutral pressure and recovered heat, with an ERV also retaining part of the indoor moisture | Tight renovations, new construction, apartments and homes with a humidifier |
Supply-only systems and humidifiers combine poorly, because slight pressurization drives humid indoor air into cold wall and attic cavities. Balanced ventilation avoids that problem and is the approach we recommend for most tight homes.
Choosing between an ERV and an HRV in New York
Both units exchange heat between outgoing and incoming air. An ERV also transfers part of the moisture. In a New York winter that keeps some indoor humidity in the house, which helps homes that run dry and can reduce the need for a humidifier. In summer it reduces the moisture carried in by ventilation air. An ERV is not a dehumidifier, however, and air conditioning or a dehumidifier is still needed in humid weather. Green Building Advisor describes the winter moisture benefit as real but modest.
An HRV removes indoor moisture in winter, which suits only houses that have too much winter humidity, such as a small, very tight house with a large family. Our practical default is an ERV for New York City and Long Island, with the choice made case by case for colder upstate homes, where core frost and defrost cycles matter more.
- Dedicated ducts give the best results. Connecting to furnace ducts is possible but requires an interlock with the blower and careful balancing.
- The outdoor intake must be separated from exhaust outlets, vents and other contaminant sources, with distances set by the applicable mechanical code.
- Airflow must be balanced with a flow measurement after installation, so that every room receives its share.
- Filters must be cleaned or replaced on schedule, and the unit placed where it can be serviced.
- Apartments can use compact ceiling ERVs or through-wall single-room units, subject to co-op or condo board approval for façade openings and, for landmarked buildings, Landmarks Preservation Commission review of visible louvers.
Kitchen range hoods and makeup air
High-heat cooking, including wok cooking, calls for a well-designed ducted hood. Yet in a tight house or apartment, a hood cannot move its rated airflow unless the same volume of air can enter. Without makeup air, a large hood creates strong negative pressure, doors whistle, odors are drawn from neighboring units, and natural-draft water heaters or boilers can spill combustion gases into the home.
Outside New York City, the residential code is based on the International Residential Code. The model IRC requires makeup air for kitchen exhaust above 400 cfm, and since its 2018 edition only where the home has natural-draft fuel-burning appliances, with a damper interlocked with the hood. We confirm the current New York State text for each project.
New York City has its own Mechanical Code, which sets its own requirements for range-hood makeup air and for dwelling ventilation. Owners should not assume that the 400 cfm figure often quoted online applies in the five boroughs. We confirm the requirement for your hood, appliances and building during design. The NYC code also permits listed recirculating hoods in many dwellings when they are installed to the manufacturer's instructions and general ventilation is provided.
- Size the hood to the cooking, not to the showroom. Rated cfm is measured at zero static pressure, and a long apartment duct with elbows and a wall cap often delivers about half.
- Capture matters as much as fan size. A deep canopy that extends beyond the cooktop often outperforms a larger fan with a shallow hood.
- Makeup air should enter through a motorized damper interlocked with the hood, be filtered, and be tempered in winter so that cold air does not spill onto the cook.
- Ducted hoods need smooth metal ducts and a backdraft damper. Opening a window is not a code-compliant makeup-air solution.
Bathroom exhaust done properly
Model codes call for at least 50 cfm intermittent or 20 cfm continuous exhaust per bathroom, and 100 cfm intermittent or 25 cfm continuous for kitchens. The NYC Mechanical Code has its own table, which we follow on city projects.
- Duct the fan to the outdoors, never into the attic or a soffit. Bath fans vented into the attic are a common cause of attic mold in Long Island capes.
- Use a short, smooth duct with a backdraft damper and a quiet fan with a low sone rating.
- Control the fan with a humidity sensor or timer so it runs for about 20 minutes after a shower.
- In apartment buildings, windowless bathrooms often share a roof exhaust shaft. Registers clogged with paint or dust are common, and booster fans cannot be added to a shared shaft without building approval.
Combustion safety and radon
Tightening a house that still has natural-draft gas appliances requires care. The standard method for combustion air provides at least 50 cubic feet of room volume per 1,000 Btu/h of appliance input. A 40,000 Btu/h water heater and an 80,000 Btu/h furnace together need about 6,000 cubic feet. Before adding a large hood or exhaust fans to such a home, a worst-case depressurization test of the appliance area should be performed, and sealed-combustion or electric replacements are worth considering.
Radon is a separate concern. On the EPA Map of Radon Zones, all five boroughs, Nassau, Suffolk, Westchester and Rockland are Zone 3, the lowest predicted potential, while Orange, Putnam, Dutchess and much of upstate New York are Zone 1. EPA advises testing every home regardless of zone, fixing at 4 pCi/L or higher and considering a fix between 2 and 4 pCi/L. Exhaust-only ventilation can increase soil-gas entry. Radon testing and mitigation should be performed by a certified radon professional, and we coordinate ventilation design with their findings.
Filtration and the right approach for your home
EPA recommends a filter rated at least MERV 13, or as high as the system fan and filter slot can accommodate. A 1-inch MERV 13 filter in an undersized return restricts airflow, which can cause coil icing, noise and higher energy use. A 4 or 5 inch media cabinet usually solves this. ERV filters protect the core and need upgrading if they are also meant to clean the air. For homes without ducts, portable HEPA purifiers are a practical complement, especially on wildfire smoke days such as those New York experienced in 2023.
| Home type | Recommended approach |
|---|---|
| Forced-air house with a gas furnace | ERV with dedicated ducts or interlocked with the furnace, 4 inch MERV 13 media filter, combustion safety check |
| Heat pump house | ERV with dedicated ducts, media filter sized to the air handler |
| Radiator or steam-heated house | Ceiling or wall ERVs serving bedrooms and living areas, quality bath fans, portable HEPA purifiers |
| Gut-renovated brownstone | Ducted ERV planned before walls close, hood makeup air designed to the NYC Mechanical Code |
| Co-op or condo apartment | Compact or through-wall ERV and a right-sized hood, subject to board approval |
| New all-electric building | Balanced ERV ventilation and a ducted hood, with makeup air confirmed during design |
Planning a kitchen with a powerful hood, a gut renovation or a tighter home is the right moment to design ventilation. We design ERV or HRV systems, range-hood makeup air and bath exhaust to the code that applies to your property, coordinate board and permit requirements, and install the work with our licensed HVAC partner.
Frequently asked questions
Is an ERV or an HRV better for a New York City home?
For most homes in New York City and on Long Island, an ERV. It retains some indoor moisture in winter and brings in less humidity in summer. An HRV suits mainly homes that have excess winter humidity. Neither unit replaces air conditioning or a dehumidifier.
Does my range hood need makeup air in NYC?
It depends on the hood, the appliances and the building, and the NYC Mechanical Code sets its own requirement that differs from the 400 cfm rule often cited for other areas. We confirm the requirement during design and include an interlocked makeup-air damper where it is needed.
Is a fresh-air system the same as an ERV?
The term fresh-air system, widely used in China, often refers to a filtered supply system designed mainly for outdoor PM2.5. In New York, the main reasons to ventilate are moisture, cooking pollutants, carbon dioxide and combustion safety, so we usually recommend a balanced ERV with good filtration as a supporting feature.
Sources
- You Probably Need an ERV, Not an HRV · Green Building Advisor
- What's Cooking? - A Look at Domestic Kitchen Exhaust Design · Polise Consulting Engineers
- Combustion Safety in the Codes · U.S. Department of Energy, Building America
- What is a MERV rating? · U.S. Environmental Protection Agency
- New York - EPA Map of Radon Zones · U.S. Environmental Protection Agency
General information only, not legal or engineering advice. Rules change and every building is different. Confirm requirements with the Department of Buildings, your local building department or your building management.